CÓDIGO DE ALARMA |
Descripción |
|
1 |
Error de escritura de la memoria |
|
2 |
Sonda Entrada agua rota o desconectada |
|
3 |
Sonda Salida agua rota o desconectada |
|
4 |
Sonda Aire exterior rota o desconectada |
|
5 |
Sonda Batería rota o desconectada |
|
6 |
Sonda Descarga rota o desconectada |
|
7 |
Sonda Aspiración rota o desconectada |
|
8 |
Transductor AP roto o desconectado |
|
9 |
Transductor BP roto o desconectado |
|
10 |
Alarma bajo calentamiento (EVD) |
|
11 |
Alarma LOP (EVD) |
|
12 |
Alarma MOP (EVD) |
|
13 |
Alarma alta temperatura Condensación (EVD) |
|
14 |
Alarma baja temperatura de aspiración (EVD) |
|
15 |
Alarma válvula (EVD) |
|
16 |
Autotuning válvula (EVD) |
|
17 |
Cierre de emergencia válvula (EVD) |
|
18 |
Alarma Rango error (EVD) |
|
19 |
Alarma Válvula valor pin fuera de límite |
|
20 |
Alarma flujostato |
|
21 |
Alarma antihielo |
|
22 |
Alarma Magnetotérmico bomba |
|
23 |
Alarma baja presión |
|
24 |
Alarma alta presión |
|
25 |
Alarma baja presión grave |
|
26 |
Alarma magnetotérmico ventilador |
|
27 |
Temperatura elevada de gas impelente: |
|
28 |
Válvula de inversión de ciclo averiada: Bajo delta P. La válvula de inversión del ciclo podría estar averiada o bloqueada |
|
29 |
Delta P mayor que el permitido en el start up (por defecto = 20 bar). No causa bloqueo de la máquina |
|
30 |
Compresor Force Off |
|
31 |
Alarma Superación de tiempo de límites operativos |
|
32 |
Arranque fallido compresor. No causa bloqueo de la máquina |
|
33 |
Diferencial de presión inferior al especificado (0,3 bar en 60 seg) |
|
34 |
Sobrecorriente |
|
35 |
Sobrecarga motor compresor |
|
36 |
Exceso de tensión CC BUS |
|
37 |
Insuficiente tensión CC BUS |
|
38 |
Exceso de temperatura drive |
|
39 |
Insuficiente temperatura drive |
|
40 |
Exceso de corriente Hardware |
|
41 |
Exceso de temperatura compresor |
|
42 |
Error módulo IGBT – Fallo interno. Sustituir Inverter |
|
43 |
Error CPU. |
|
44 |
Parámetros por defecto |
|
45 |
CC bus ripple. Controlar las tensiones de las fases que alimentan el inverter |
|
46 |
Comunicación entre inverter y uPC3 ausente |
|
47 |
Fallo en sensor de temperatura drive |
|
48 |
Autoconfiguración fallida |
|
49 |
Drive inverter inhabilitado. Controlar puentes en caja de conexiones de inverter Power Plus |
|
50 |
Error de fases motor |
|
51 |
Ventilador de refrigeración inverter averiado |
|
52 |
Speed fault. Pérdida de potencia del compresor. Controlar tipo de compresor configurado |
|
53 |
PFC fault (alarma que se verifica con PFC habilitado mientras el bus CC está muy bajo) |
|
54 |
PFC overload trip (esta alarma no estará presente en las nuevas versiones del firmware) |
|
55 |
Input voltage error (cuando la alimentación baja de los 170 V con el motor en movimiento) |
|
56 |
Error STO 1 |
|
57 |
Error STO 2 |
|
58 |
Fallo de la conexión a tierra (solo para monofásica) |
|
59 |
Internal error 1 (ADC conversion sync fault) |
|
60 |
Internal error 2 (Hw sync fault) |
|
CÓDIGO DE ALARMA |
Descripción |
|
61 |
Inverter drive overload |
|
62 |
uC safety Drive Stopped |
|
63 |
99:Inverter unexpected stop |
|
64 |
Inverter offline |
|
65 |
01:Inverter uSafety current measurement fault |
|
66 |
02:Inverter uSafety current unbalanced fault |
|
67 |
03:Inverter uSafety over current |
|
68 |
04:Inverter uSafety STO alarm |
|
69 |
05:Inverter uSafety STO hardware alarm |
|
70 |
06:Inverter uSafety main power supply missing |
|
71 |
07:Inverter uSafety HW fault on inverter command buffer |
|
72 |
08:Inverter uSafety HW fault on heater circuitry |
|
73 |
09:Inverter uSafety data communication fault |
|
74 |
10:Inverter uSafety compressor stall detect |
|
75 |
11:Inverter uSafety DC bus over current |
|
76 |
12:Inverter uSafety HWF DC bus current alarm |
|
77 |
13:Inverter uSafety DC bus voltage alarm |
|
78 |
14:Inverter uSafety HWF DC bus voltage alarm |
|
79 |
15:Inverter uSafety input voltage alarm |
|
80 |
16:Inverter uSafety HWF input voltage alarm |
|
81 |
Alta presión de presostato |
|
82 |
Alarma resumen Térmicas |
|
83 |
Desescarche forzado por alta temperatura de gas impelente |
|
84 |
Alarma alta temperatura entrada de agua |
|
85 |
Alarma force off bajo contenido de agua |
|
86 |
Error carga parámetros inverter |
|
87 |
Inverter no compatible con el seleccionado |
|
88 |
Arranque fallido espera de siguiente intento |
|
89 |
Número máximo de arranques fallidos |
|
90 |
Alta temperatura gas impelente de envolvente |
|
91 |
Alarma envolvente zona 2: elevada relación de compresión |
|
92 |
Alarma envolvente zona 3: alta temperatura gas impelente |
|
93 |
Alarma envolvente zona 4: elevada corriente compresor |
|
94 |
Alarma envolvente zona 5: baja presión de aspiración |
|
95 |
Alarma envolvente zona 6: baja relación de compresión |
|
96 |
Alarma envolvente zona 7: bajo diferencial de presión |
|
97 |
Alarma envolvente zona 8: baja presión de descarga |
|
98 |
Alarma envolvente zona 9: baja presión de aspiración |
|
99 |
Alarma envolvente zona 10: alta temperatura gas impelente |
|
100 |
17:Inverter uSafety DC bus power alarm |
|
101 |
18:Inverter uSafety HWF power mismatch |
|
102 |
19:Inverter uSafety NTC over temperature |
|
103 |
20:Inverter uSafety NTC under temperature |
|
104 |
21:Inverter uSafety NTC fault |
|
105 |
22:Inverter uSafety HWF sync fault |
|
106 |
23:Inverter uSafety invalid parameter |
|
107 |
24:Inverter uSafety FW fault |
|
108 |
25:Inverter uSafety HW fault |
|
109 |
26:Inverter uSafety – reseved |
|
110 |
27:Inverter uSafety – reseved |
|
111 |
28:Inverter uSafety – reseved |
|
112 |
29:Inverter uSafety – reseved |
|
113 |
30:Inverter uSafety – reseved |
|
114 |
31:Inverter uSafety – reseved |
|
115 |
32:Inverter uSafety – reseved |
|
116 |
Sonda Remota DHW averiada |
|
117 |
Fallo Sonda entrada multifunción (acumulación instalación) |