AUTODIAGNOSTICO – TABLA 5 |
|||||
TABLA DE FUNCIONES DE AUTODIAGNÓSTICO MODELO CORRESPONDIENTES: U.I. MULTI INVERTER (R410A) ASH7LMACW – ASH9LMACW – ASH12LMACW |
|||||
Large division indication |
Small division indication is indicated by pushing TEST RUN |
||||
Error contents |
Error display |
Error contents |
Error display |
||
OPERATION (RED) |
TIMER (GREEN) |
OPERATION (RED) |
TIMER (GREEN) |
||
Indoor unit sensors error Sondas unidad interior |
2 times |
|
Indoor unit room temperature sensor error Sonda ambiente unidad interior |
|
2 times |
Indoor unit piping sensor wire Sonda tubo unidad interior |
|
3 times |
|||
Control unit error (indoor unit) Control unidad interior |
4 times |
|
MANUAL AUTO button error Boton MANUAL AUTO |
|
2 times |
Power source Hz decision error Error detección frecuencia alimentación |
|
4 times |
|||
Serial error Error de comunicación |
5 times |
|
Serial reverse transmission error Error comunicación de unid. exterior a interior |
|
2 times |
Serial forward transmission error Error comunicación de unid. exterior a interior |
|
3 times |
|||
Fan motor error Ventialdor interior |
6 times |
|
Lock error Error bloqueo ventilador int. |
|
2 times |
R.p.m. Error Error velocidad giro anormal |
|
3 times |
|||
Outdoor unit sensors error Sondas unidad exterior |
|
2 times |
Discharge thermistor error Sonda temperatura de descarga |
2 times |
|
Heat exchanger thermistor error Sonda disipador modulo IPM |
4 times |
|
|||
Outdoor temperature thermistor error Sonda ambiente unidad exterior |
6 times |
|
|||
Compressor thermistor error Sonda temperatura compresor |
8 times |
|
|||
2 way valve thermistor error Sonda temperatura válvula de 2 vías |
9 times |
|
|||
3 way valve thermistor error Sonda temperatura válvula de 3 vías |
10 times |
|
|||
Pressure switch error Presostato de alta |
|
3 times |
Pressure switch error Presostato alta activado |
2 times |
|
Control unit error (outdoor unit) Control unidad exterior |
|
4 times |
Capacity error of connecting indoor unit Error de capacidad unid. interioes conectadas |
2 times |
|
Inverter error Error Inverter |
|
5 times |
Outdoor unit IPM error Error del modulo IPM |
2 times |
|
Compressor loter location error No se detecta posicion del rotor del compresor |
5 times |
|
AUTODIAGNOSTICO – TABLA 6 |
|||
TABLA DE FUNCIONES DE AUTODIAGNÓSTICO MODELOS CORRESPONDIENTES: U.I. MULTI INVERTER F (R410A) AS*18LBAJ – AS*24LBAJ AU*12LBAB – AU*14LBAB – AU*18LBAB AB*14LBAJ – AB*18LBAJ – AB*24LBAJ |
|||
Error contents / CONTENIDO DE ERRORES |
Error display |
||
OPERATION (RED) |
TIMER (GREEN) |
SWING (ORANGE) |
|
Indoor unit circuit board error (EEPROM) Error circuito placa unidad interior (EEPROM) |
|
|
|
Indoor unit room temperature sensor wire opened Sonda ambiente unidad interior abierta |
2 times |
|
|
Indoor unit room temperature sensor wire short circuited Sonda ambiente unidad interior en corto |
2 times |
|
|
Indoor unit piping sensor wire opened Sonda tubo unidad interior abierto |
3 times |
|
|
Indoor unit piping sensor short circuited Sonda tubo unidad interior en corto |
3 times |
|
|
Drain pump error Alarma bomba condensados |
4 times |
|
|
Reverse signal error (outdoor unit —> indoor unit) Error de comunicación de unidad exterior a unidad interior |
5 times |
|
|
Forward signal error ( indoor unit —> outdoor unit) Error de comunicación de unidad interior a unidad exterior |
5 times |
|
|
Indoor unit fan error Error ventilador unidad interior |
6 times |
|
|
Outdoor unit piping sensor Sonda tubo unidad exterior |
|
3 times |
|
Outdoor unit outdoor temperature sensor error Sonda ambiente unidad exterior |
|
4 times |
|
Outdoor unit discharge temperature sensor error Sonda temperatura de descarga |
|
5 times |
|
Outdoor unit compressor temperature sensor error Sonda temperatura compresor |
|
8 times |
|
Outdoor unit pressure switch error Presostato alta activado |
|
9 times |
|
IPM error Error del modulo IPM |
|
10 times |
|
CT error Error CT (transformador de corriente) |
|
11 times |
|
Active Filter Module (AFM) error Error de filtro activo de potencia (AFM) |
|
12 times |
|
Compressor rotor position cannot detect No se detecta la posicion del rotor del compresor |
|
13 times |
|
Outdoor fan motor error Error ventilador unidad exterior |
|
14 times |
|
Outdoor unit 2 way valve temperature sensor error Error de sonda de temperatura de valvula de 2 vias |
|
|
2 times |
Outdoor unit 3 way valve temperature sensor error Error de sonda de temperatura de valvula de 3 vias |
|
|
3 times |
Idoor unit connection capacity error Error de potencia de unidad inteior conectada |
|
|
4 times |
Communication error (inverter – multicontroller) Error de comunicación (inverter – multicontroller) |
|
|
5 times |
AUTODIAGNOSTICO – TABLA 7 |
|
TABLA DE FUNCIONES DE AUTODIAGNÓSTICO MODELOS CORRESPONDIENTES: U.I. MULTI INVERTER F (R410A) AR*9LUAB – AR*12LUAD – AR*14LUAD – AR*18LUAD – AR*22LUAD |
|
Error code |
Error contents |
00 |
Communication error (indoor unit <—-> remote controller) Error de comunicación entre unidad interior y mando por cable |
01 |
Reverse signal error (outdoor unit —> indoor unit) Error de comunicación de unidad exterior a unidad interior |
02 |
Room temperature sensor open Sonda ambiente unidad interior abierta |
03 |
Room temperature sensor short-circuited Sonda ambiente unidad interior en corto |
04 |
Indoor heat exchanger temperature sensor open Sonda tubo unidad interior abierta |
05 |
Indoor heat exchanger temperature sensor short-circuited Sonda tubo unidad interior en corto |
06 |
Outdoor heat exchanger temperature sensor Sonda tubo unidad exterior |
08 |
Power source connection error Error alimentación |
09 |
Float switch operated Alarma bomba condensados |
0A |
Outdoor temperature sensor Sonda ambiente unidad exterior |
0c |
Discharge pipe temperature sensor Sonda temperatura de descarga |
0E |
Outdoor high pressure abnormal Protección alta presión en frío |
11 |
Model abnormal Modelos incompatibles |
12 |
Indoor fan abnormal Error ventilador unidad interior |
13 |
Forward signal error ( indoor unit —> outdoor unit) Error de comunicación de unidad interior a unidad exterior |
14 |
Outdoor EEPROM abnormal Error EEPROM unidad exterior |
15 |
Compressor temperature sensor Sonda temperatura compresor |
16 |
Pressure switch error Presostato alta activado |
17 |
IPM error Error del modulo IPM |
18 |
CT error Error CT (transformador de corriente) |
19 |
Active Filter Module (AFM) error Error de filtro activo de potencia (AFM) |
1A |
Compressor does not operate Compresor no puede arrancar |
1b |
Outdoor unit fan error Error ventilador exterior |